The Flowfit CPA240 flow assembly is designed for all demanding applications where high temperatures and pressures are involved. With its various connections, Flowfit flexibly adapts to your process offering space for three sensors. Simple installation and removal of the sensors save time for maintenance and recalibration.
Flowfit CPA240 is intended to be used in pipes in:
Chemical industry
Petrochemical industry
Power plants and waste incinerating plants
Extractive metallurgy and metal processing
Drinking water treatment plants
It is suitable for use with pressures of up to 10 bar (stainless steel) or 8 bar (PVDF).
Benefits
Simple installation and removal of the electrode holder (e.g. for calibration)
Flexible connection to the process by means of various connectors and installation versions
Less condensation due to a Goretex filter
Reduces installation effort by providing 3 mounting positions for 120 mm sensors or an optional cleaning unit
Our monitoring systems provide expert wastewater analysis for the chemical industry. Read about the experience of one company that needs to monitor and report TOC levels to comply with regulations.
Kerry DCF produces spreads and butter products for the retail market. The company wanted to automate its test for chemical oxygen demand in its treated effluent to save time and optimise the process.
Discover how Heineken meets all regulations to protect the brazilian environment with the Viomax CAS51D digital nitrate or SAC sensor from Endress+Hauser.
Intuitive pH and conductivity measurement in smart vertical farming plants to meet quality requirements and ensure comprehensive
monitoring of processes.
Drinking water treatment plants, boiler feedwater and ultra-pure water plants, cooling-water circuits, fertiliser production, sugar production, gas scrubbers, petrochemical plants
Installation
Flow assembly
Characteristic
Piping, bypass
Design
3 electrode installation locations, 120mm electrodes, flow direction horizontal or from the bottom, thread connection G1/2" for spray cleaning
Material
Flow vessel: PVDF or stainless steel 1.4404 O-rings: EPDM, Viton, Chemraz or Fluoraz
Process temperature
PVDF version: 0 to 120 °C (32 to 248 °F) Stainless steel version: -15 to 150 °C (5 to 302 °F) With EPDM: -15 to 140 °C (5 to 284 °F)
Process pressure
PVDF version: max. 8 bar at 50 °C (max. 116 psi at 122 °F) Stainless steel version: max. 10 bar (max. 145 psi)
Connection
Pressurized flange DN25/PN16, ASME 1" lbs 150, JIS 10K25A
Additional certifications
Material certification 3.1.B EN 10204
Measuring principle
Sensor ORP / Redox
Application
Drinking water treatment plants, boiler feedwater and ultra-pure water plants, cooling-water circuits, fertiliser production, sugar production, gas scrubbers, petrochemical plants
Installation
Flow through holder
Characteristic
Piping, bypass
Design
3 electrode installation locations, 120mm electrodes, flow direction horizontal or from the bottom, thread connection G1/2" for spray cleaning
Material
Flow vessel: PVDF or stainless steel 1.4404 O-rings: EPDM, Viton, Chemraz or Fluoraz
Process temperature
PVDF version: 0 to 120 °C (32 to 248 °F) Stainless steel version: -15 to 150 °C (5 to 302 °F) With EPDM: -15 to 140 °C (5 to 284 °F)
Process pressure
PVDF version: max. 8 bar at 50 °C (max. 116 psi at 122 °F) Stainless steel version: max. 10 bar (max. 145 psi)
Connection
Pressurized flange DN25/PN16, ASME 1" lbs 150, JIS 10K25A